|
|
|
|
|
|
|
|
|
|
|
|
|
|
 |
|
|
|
|
 |
|
ACR JR
|
|
|
 |
|
ACR Nautilus
|
|
|
|
|
 |
|
ACR Owl
|
|
|
|
|
|
|
|
|
|
|
|
|
 |
|
ACR PowerWatch
|
|
|
|
|
 |
|
ACR Smartbutton
|
|
|
 |
|
ACR SmartReader
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
 |
|
ACR SmartReader Plus
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
 |
|
|
|
|
|
SmartReader 4 Five Channel Pressure, Temperature and Relative Humidity Data Logger
|
SmartReader 4 is a data logger for easy monitoring and troubleshooting of pneumatic systems. It is designed to work with optional plug-in ACR Pressure Modules. A bonus: the SmartReader 4 can also monitor Relative Humidity as well as remote temperature and RH (All sensors sold separately).
|
Five Channel Pressure, Temperature and Relative Humidity Data Logger
|
|
|
|
|
.
|
| Range |
Resolution |
Guage |
Absolute
|
| P/N |
Cat. # |
P/N |
Cat. #
|
| 0 to 5 psi (30kPa) |
0.03 psi (0.2kPa) |
PM-005-G |
#01-0045 |
N/A |
N/A
|
| 0 to 30 psi (200kPa) |
0.15 psi (1.0kPa) |
PM-030-G |
#01-0047 |
PM-030-A |
#01-0046
|
| 0 to 100 psi (100kPa) |
0.5 psi (3.5kPa) |
PM-100-G |
#01-0049 |
PM-100-A |
#01-0048
|
| 0 to 150 psi (1000kPa) |
0.5 psi (3.5kPa) |
PM-150-G |
#01-0086 |
N/A |
N/A
|
|
Multi-channel, Configurable, 8-Bit Data Loggers
|
| Size: |
107 X 74 X 22 mm (4.2 X 2.9 X 0.9").
|
| Weight: |
110 grams (3.75 ounces)
|
| Case Material: |
Noryl® Plastic
|
| Operating Limits: |
-40°C to 70°C (-40°F to 158°F) and 0 to 95% Relative Humidity (non-condensing).
|
| Clock Accuracy: |
+/-2 seconds per day.
|
| Battery: |
3.6 volt Lithium, 1 Amp-Hour
|
| Power Consumption: |
5 to 10 microamps (continuous).
|
| Battery Life: |
10-years warrantied (under normal use.) Factory replaceable.
|
| Mounting: |
Magnetic backing or locking eyelet.
|
| Memory Size: |
32 K (32,768 readings).
|
| Sampling Method: |
1. Continuous (First-in, First-out) 2. Stop when full (Fill-then-stop).
|
| Sampling Rate: |
User selectable rates between 8 seconds to once every 5 days.
|
| Resolution: |
8 bits (1 part in 256).
|
| External Connector: |
Removable screw-type terminal strip with Common (-) connection.
|
| PDF |
Click Here
|
| PC Requirements: |
IBM PC or 100% compatible running MS® Windows 3.1, '95, '98, or NT, with at least 2 MB RAM, 2 MB of hard drive disk space and one free serial port.
|
Product Approvals: |
Meets Part 15 for Digital Devices of the Code of Federal Regulations of the Federal Communications Commision (FCC). Meets Class A radiated and conducted emission requirements of Section 2 of the Radio Interference Regulations of Communications Canada. IEC801-2, 3, 4 and EN55011 covering ESD, RFI Immunity, EFT/Burst and Radiated Emissions respectively, for the Commission of the European Communities (CE).
|
Resistance to X-Rays: |
Tested for protection against a 160kV dose @ 5mA for 30 seconds (150mA-sec) @ 38 inches F.F.D. (about 100 times that of an airport X-Ray machine). Tested for protection against Gamma Ray (equivalent to 0.137 - 1.38 mega volts) IR 192 - 28 curies @ 30 second exposure source to object distance 5".
|
Internal Temperature Sensor
|
Type: |
Negative Temperature Coefficient Thermistor. 10,000 ohms @ 25°C (77°F).
|
Tolerance (sensor only): |
+/-0.2°C, over the range of 0 to 70°C (+/-0.3°F, over the range of 32 to 158°F).
|
Range: |
-40° to 70°C (-40° to 158°F).
|
Resolution: |
0.4°C (0.7°F) @ 25°C. Better than 1°C (1.8°F) between -25°C (-13°F) and 70°C (158°F). Better than 2.0°C (3.6°F) between -40°C (-40°F) and 25°C (-13°F)
|
|
PC to SmartReader Communications
To setup, download or view realtime information from an ACR SmartReader Data Logger, all that is required is an ACR IC-101 Interface Cable. Connection is simple. Plug the IC-101 connector into your PC's serial port and the stereo cable into the ACR Data Logger. The IC-101 cable is included with the ACR TrendReader Interface Package. No tools, interface cards or docking stations required. You can setup, download or view realtime information from up to 8 loggers at once, locally or over a modem.
|
|
TrendReader® Software
TrendReader® for Windows® is a powerful, versatile, and easy to use software package designed exclusively for ACR's SmartReader, SmartReader Plus and OWL Data Loggers. Powerful features and easy setup enables logged data to be collected and thoroughly analyzed in seconds. |
|
Fast and Easy Logger Setup
Since TrendReader® comes complete with built-in menus for Sample Rate, Start Delay, Equations and more, setup is fast and easy. In addition, equations are already included for all ACR accessories so users need only select the appropriate equation from the menu. Realtime readings are displayed in the Setup window, allowing you to ensure that your logger's setup is correct before placing it in the field. |
|
One-Touch Table View
With ACR's TrendReader® Software, logged data can be viewed in Table format to permit detailed analysis of logged data. Multiple channels of data can be displayed at once with each reading displaying the time and date. You can even select portions of, or all the table information and paste it into your favorite Windows® presentation or word processing program.
|
|
Presentation Quality Graphs
TrendReader® allows you to present logged data the way you want. Multiple logged data sets can be displayed and compounded to create new graphs. For added presentation power, TrendReader® lets you add comments, change graph colors, zoom in on specific portions of data, display your data using custom engineering units and print to any Windows® compatible printer with ease. TrendReader® even lets you copy/paste your graphs directly into your case reports. If you prefer to use Excel,® Lotus® or other popular spreadsheet programs, data can be exported into ASCII and CSV formats.
|
|
|
|