Search This Site

(Search by Product Type i.e. Level or Brand Name i.e. Walchem)

PD2-6060 Helios Dual Analog Input Process Meter

USA Toll Free: 1-800-730-0302 Tel: 416-240-1920 - sales@metexcorporation.com


What sets the Helios apart from other Large Display Meters is its dual line display with super bright LEDs that can be read even in bright sunlight and up to 100 feet away. Based on Precision Digital's popular line of ProVu® digital panel meters, the Helios can satisfy a wide variety of level, flow, temperature, pressure, & weight applications. It is available with models that accept 4-20 mA, thermocouple, RTD, pulse, strain gauge, AC and DC volts and current, and even Modbus®.

 

Go with the Helios PD2-6060 when you need a large display meter to display two 4-20 mA inputs on one meter. Both of these inputs can be displayed on six full digits and each transmitter is provided with its own 24 VDC transmitter power supply. The PD2-6060 can also perform a variety of math functions on those two inputs, such as computing the difference between them or summing them together.


Input

  • Two (2) 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V

Helios Features

  • Large 1.80" Digits
  • Dual Line Display
  • Six Full Digits on Each Line
  • Readable From 100 Feet Away
  • Superluminous Sunlight Readable Display
  • NEMA 4X, IP65 Rated Field Mountable Enclosure
  • Great for Outdoor Use: -40 to 150°F (-40 to 65°C)
  • Program the Meter from a PC with Onboard USB and MeterView® Pro

PD2-6060 Features

  • Displays Two Process Inputs Simultaneously
  • Math Functions Capabilities
  • Isolated 24 VDC @ 200 mA Transmitter Power Supply
  • Multi-Pump Alternation Control
  • Signal Input Conditioning for Flow & Round Horizontal Tank
  • Programmable Displays & Function Keys
  • 32-Point, Square Root, or Exponential Linearization
  • Current Input Protected by Resettable Fuse
  • Tare Function

PD2-6060 Helios Dual Analog Input Process Meter Data Sheet

PD2-6060 Helios Dual Analog Input Process Meter Instruction Manual

General Specifications

  • Display: Two lines with 1.8" (46 mm) high digits, red LEDs; 6 digits per line (-99999 to 999999), with lead zero blanking
  • Display Intensity Eight user selectable intensity levels
  • Display Update Rate: 5/second (200 ms)
  • Overrange: Display flashes 999999
  • Underrange: Display flashes -99999
  • Display Assignment: Display lines 1 & 2 may be assigned to process values for Channels A (Ch-A), B (Ch-B), or C (Ch-C), toggle between (Ch-A & Ch-B, Ch-A & Ch-C, Ch-B & Ch-C, and Ch-A, Ch-B, & Ch-C), toggle between Channel & units, show channel gross value (no tare) or toggle net (tare) and gross values, show relay set points, max & min values, or Modbus input. The lower display may also be set to show engineering units or be off, with no display.
  • Programming Methods: Four programming buttons, digital inputs, PC and MeterView Pro software, or Modbus registers.
  • Noise Filter: Programmable from 2 to 199 (0 will disable filter)
  • Filter Bypass: Programmable from 0.1 to 99.9% of calibrated span
  • Recalibration: All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
  • Max/Min Display: Max/min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
  • Password: Three programmable passwords restrict modification of programmed settings.
    Pass 1: Allows use of function keys and digital inputs
    Pass 2: Allows use of function keys, digital inputs and editing set/reset points
    Pass 3: Restricts all programming, function keys, and digital inputs.
  • Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or 12-24 VDC ± 10%, 15 W max. Powered over USB for configuration only.
  • Isolated Transmitter Power Supply: Terminals P+ & P-: 24 VDC ± 10%. 12-24 VDC powered models selectable for 24, 10, or 5 VDC supply (internal P+/P- switch). 85-265 VAC models rated @ 200 mA max, 12-24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply.
  • Non-Volatile Memory: All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
  • Fuse: Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse
  • Normal Mode Rejection: Greater than 60 dB at 50/60 Hz
  • Isolation: 4 kV input/output-to-power line; 500 V input-to-output or output-to-P+ supply
  • Overvoltage Category: Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
  • Environmental: Operating temperature range: -40 to 150°F (-40 to 65°C); Storage temperature range: -40 to 185°F (-40 to 85°C); Relative humidity: 0 to 90% non-condensing
  • Connections: Removable and integrated screw terminal blocks accept 12 to 22 AWG wire.
  • Enclosure: UL Type 4X, IP65 rated. Polycarbonate & glass blended plastic case, color: gray. Includes four PG11 through-hole conduit openings, with two factory installed PG11, IP68, black nylon threaded hole plugs with backing nuts.
  • Wall Mounting: Four (4) mounting holes provided for mounting meter to wall.
  • Pipe Mounting: Optional pipe mounting kit (PDA6260) allows for pipe mounting. Sold separately.
  • Overall Dimensions: 10.63" x 12.59" x 4.77" (270 mm x 319.7 mm x 121.2 mm) (H x W x D)
  • Weight: 6.10 lbs (2.76 kg)
  • UL File Number: UL & C-UL Listed. E160849; 508 Industrial Control Equipment.
  • Warranty: 3 years parts & labor
  • USB Connection: Compatibility: USB 2.0 Standard, Compliant Connector Type: Micro-B receptacle Cable: USB A Male to Micro-B Cable Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit, Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit Power: USB Port

Dual Process Input

  • Two Inputs: Two non-isolated inputs, each separately field selectable: 0-20, 4-20 mA, ±10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave)
  • Channels: Channel A, Channel B, Channel C (Math channel)Programmable Constants:Constant P (Adder): -99.999 to 999.999, default: 0.000; Constant F (Factor): 0.001 to 999.999, default: 1.000
  • Sequence Of Operations For Input Programming:1.Select Input for A and B
    2.Set up the engineering units for A, B, and C
    3.Set up decimal point for A, B, and C
    4.Program A & B
    5.Set up the displays for A, B, or C
    6.Select the transfer function for A & B (e.g. Linear)
    7.Select Math function for Channel C
    8.Program constants for Factor (F) and Adder (P)
    9.Program cutoff values for A and B
  • Accuracy: ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span
  • Temperature Drift: 0.005% of calibrated span/°C max from 0 to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 0°C ambient
    Signal Input Conditioning: Linear, square root, programmable exponent, or round horizontal tank volume calculation
  • Multi-Point Linearization: 2 to 32 points for channel A and B
  • Programmable Exponent: 1.0001 to 2.9999
  • Round H Tank: Diameter & Length: 999.999 inch or cm calculates volume in gallons or liters respectively.
  • Low-Flow Cutoff: 0-999999 (0 disables cutoff function)
  • Decimal Point: Up to five decimal places or none: d.ddddd, d.dddd, d.ddd, d.dd, d.d, or dddddd
  • Input Impedance: Voltage ranges: greater than 500 kO; Current ranges: 50 - 100 ? (depending on resettable fuse impedance)
  • Input Overload: Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed.
  • HART Transparency: Analog input will not interfere with existing HART communications on the wired 4-20 mA signal
  • F4 Digital Input Contacts: 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
  • F4 Digital Input Logic Levels: Logic High: 3 to 5 VDC, Logic Low: 0 to 1.25 VDC

Relays

  • Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (˜ 50 W) @ 125/250 VAC for inductive loads
  • Noise Suppression: Noise suppression is recommended for each relay contact switching inductive loads. See manual for details.
  • Deadband: 0-100% of span, user programmable
  • High Or Low Alarm: User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turn off).
  • Relay Operation: Automatic (non-latching) and/or manual reset; Latching (requires manual acknowledge) with/without clear; Pump alternation control (2 to 4 relays); Sampling (based on time); Off (disable unused relays and enable Interlock feature); Manual on/off control mode
  • Relay Reset: User selectable via front panel buttons or digital inputs
    1. Automatic reset only (non-latching), when the input passes the reset point.
    2. Automatic + manual reset at any time (non-latching)
    3. Manual reset only, at any time (latching)
    4. Manual reset only after alarm condition has cleared (latching)
    Note: Front panel button or digital input may be assigned to acknowledge relays programmed for manual reset.
  • Time Delay: 0 to 999.9 seconds, on & off relay time delays; Programmable and independent for each relay
  • Fail-Safe Operation: Programmable and independent for each relay. Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm
    state.
  • Auto Initialization: When power is applied to the meter, relays will reflect the state of the input to the meter.

Isolated 4-20 mA Transmitter Output

  • Isolated 4-20 mA Transmitter Output
  • Output Source: Process variable (PV), max, min, set points 1-4, Modbus input, or manual control mode
  • Scaling Range: 1.000 to 23.000 mA for any display range
  • Calibration: Factory calibrated: 4.000 to 20.000 = 4-20 mA output
  • Analog Out Programming: 23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break
  • Accuracy: ± 0.1% of span ± 0.004 mA
  • Temperature Drift: 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient
    Note: Analog output drift is separate from input drift.
  • Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC ± 10%. Isolated from the input at >500 V. May be used to power the 4-20 mA output or other devices. All models rated @ 40 mA max.

RS485 Serial Communications Terminal

  • Compatibility: EIA-485
  • Connectors: Removable screw terminal connector
  • Max Distance: 3,937' (1,200 m) max
  • Status Indication: Separate LEDs for Power (P), Transmit (TX), and Receive (RX)
  • Modbus® RTU Serial Communications Protocol
  • Slave: ID 1 – 247 (Meter address)
  • Baud Rate: 300 – 19,200 bps
  • Transmit Time Delay: Programmable between 0 and 199 ms
  • Data: 8 bit (1 start bit, 1 or 2 stop bits)
  • Parity: Even, Odd, or None with 1 or 2 stop bits
  • Byte-To-Byte Timeout: 0.01 – 2.54 second
  • Turn Around Delay: Less than 2 ms (fixed)
    Note: Refer to the Modbus Register Tables located at www.predig.com for details.

Digital Input & Output Terminal

  • Channels: 4 digital inputs & 4 digital outputs
  • Digital Input Logic High: 3 to 5 VDC
  • Digital Input Logic Low: 0 to 1.25 VDC
  • Digital Output Logic High: 3.1 to 3.3 VDC
  • Digital Output Logic Low: 0 to 0.4 VDC
  • Source Current: 10 mA maximum output current
  • Sink Current: 1.5 mA minimum input current
  • +5 V Terminal: To be used as pull-up for digital inputs only. Connect normally open pushbuttons across +5 V & DI 1-4
    .
    WARNING! DO NOT use +5 V terminal to power external devices.

 

METEX CORPORATION LIMITED

About Us

Metex Corporation Limited has been providing superior products and services to the process control, chemical treatment, waste water, industrial and manufacturing industries for over 25 years. It is our goal to continually provide our customers with the best possible equipment, technology, and service.

Sitemap

Our Products

Dataloggers, sensors, pumps, recorders, hand held instruments, flow instrumentation, level controls, valves, instrumentation, containers, tanks, transmitters, data loggers, digital indicators, mixers and agitators, pressure intrumentation, analyzers and controllers for a variety of industrial applications such as water quality, pH/ORP and more.

Website Content

Water Analyzers and Controllers, Wireless Products, Corrosion Monitoring Equipment, Cooling Tower and Boiler Controllers, a wide variety of Pumps, Valves, Dataloggers and Recorders, HVAC, Instrumentation, Skids and Systems, Containers and Tanks from world leading manufacturers are products you will find on this site.

Get in Touch