The PD6000 is a member of the ProVu series of 1/8 DIN digital panel
meters that accepts a process current (4-20 mA) or process voltage
(0-5V, 1-5V, etc.) signal. It displays that signal on a dual-line,
6-digit display that is available with optional Sunbright® sunlight
readable LEDs. Like all ProVu meters, the PD6000 includes UL / C-UL
listing and CE marking, a NEMA 4X front, and AC or DC power options.
ProVu meters can be equipped with up to four internal relays, a 4-20
mA output and Modbus® RTU serial communications. The PD6000 includes
a 24 VDC power supply to drive the transmitter and can be programmed
via the front panel pushbuttons or with the onboard USB and MeterView®
Pro software.
Features
0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs
NEMA 4X, IP65 Front
Universal 85-265 VAC or 12-24 VDC Input Power
Large Dual-Line 6-Digit Display, 0.60" & 0.46"
Dual-Scale for Level Applications Single Input
Optional SunBright Display Models for Outdoor Applications
Isolated 24 VDC @ 200 mA Transmitter Power Supply
Signal Input Conditioning for Flow & Round Horizontal Tanks
Programmable Displays & Function Keys
32-Point, Square Root, or Exponential Linearization
Multi-Pump Alternation Control
2 or 4 Relays + Isolated 4-20 mA Output Options
External 4-Relay & Digital I/O Expansion Modules
USB, RS-232, & RS-485 Serial Communication Options
Tare Function
Modbus RTU Communication Protocol Standard
On-Board Digital Input
Configure, Monitor, and Datalog
Onboard USB and MeterView® Pro Programming Software
Display: Upper display: 0.60" (15 mm) high. Lower display:
0.46" (12 mm) high. Both are 6 digits (-99999 to 999999), red
LEDs.
Display Intensity: Eight intensity levels
Display Update Rate: 5/second (200 ms)
Overrange: Display flashes 999999
Underrange: Display flashes -99999
Display Assignment: The upper and lower displays may be assigned
to PV1, PV2, PCT (percent), d r-u, d gross, d nt-g, max/min, alternate
max & min, set points, units (lower display only), or Modbus
input.
Front Panel: NEMA 4X, IP65
Programming Methods: Four front panel buttons, digital inputs,
PC and MeterView Pro software, Modbus registers.
F4 Digital Input Contacts: 3.3 VDC on contact. Connect normally
open contacts across F4 to COM.
F4 Digital Input Logic Levels: Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC
Noise filter: Programmable from 2 to 199 (0 will disable filter)
Filter Bypass: Programmable from 0.1 to 99.9% of calibrated span
Recalibration: Calibrated at the factory. Recalibration is recommended
at least every 12 months.
Max/Min Display: Max / min readings reached by the process are
stored until reset by the user or until power to the meter is turned
off.
Password: Three programmable passwords restrict modification of
programmed settings.
Non-Volatile Memory: All programmed settings are stored in nonvolatile
memory for a minimum of ten years if power is lost.
Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or 12-24
VDC ± 10%, 15 W max. Powered over USB for configuration only.
Fuse: Required external fuse: UL Recognized, 5 A max, slow blow;
up to 6 meters may share one 5 A fuse.
Isolated Transmitter Power Supply:Terminals P+ & P-: 24 VDC
± 10%. 12-24 VDC powered models selectable for 24, 10, or
5 VDC supply (internal P+/P- switch). 85-265 VAC models rated @
200 mA max, 12-24 VDC powered models rated @ 100 mA max, @ 50 mA
max for 5 or 10 VDC supply.
Normal Mode Rejection: Greater than 60 dB at 50/60 Hz
Isolation: 4 kV input/output-to-power line. 500 V input-to-output
or output-to-P+ supply.
Overvoltage Category: Installation Overvoltage Category II: Local
level with smaller transient overvoltages than Installation Overvoltage
Category III.
Environmental:
Operating temperature range: -40 to 65°C
Storage temperature range: -40 to 85°C
Relative humidity: 0 to 90% non-condensing
Connections: Removable screw terminal blocks accept 12 to 22 AWG
wire, RJ45 for external relays, digital I/O, and serial communication
adapters.
Enclosure: 1/8 DIN, high impact plastic, UL 94V-0, color: black
Mounting: 1/8 DIN panel cutout required: 3.622" x 1.772"
(92 mm x 45 mm). Two panel mounting bracket assemblies are provided.
Decimal Point: Up to five decimal places or none: d.ddddd, dd.dddd,ddd.ddd,
dddd.dd, ddddd.d, or dddddd.
Calibration Range: 4-20 mA: minimum span input 1 & input 2:
0.15 mA. ±10 V: minimum span input 1 & 2: 0.10 V. An
Error message will appear if input 1 and input 2 signals are too
close together.
Input Impedance: Voltage ranges: greater than 500 kO. Current
ranges: 50 - 100 O (depending on resettable fuse impedance).
Input Overload:Current input protected by resettable fuse, 30
VDC max.
HART Transparency: Analog input will not interfere with existing
HART communications on the wired 4-20 mA signal
Relays
Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external;
rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (
50 watts) @ 125/250 VAC for inductive loads such as contactors,
solenoids, etc.
Noise Suppression: Noise suppression is recommended for each relay
contact switching inductive loads.
Deadband: 0-100% of span, user programmable
High or Low Alarm: User may program any alarm for high or low
trip point. Unused alarm LEDs and relays may be disabled (turned
off).
Relay Operation: automatic (non-latching), latching (requires
manual acknowledge), sampling (based on time), pump alternation
control (2 to 8 relays), Off (disable unused relays and enable interlock
feature, manual on/off control mode).
Relay Reset: User selectable via front panel buttons or digital
inputs.
1. Automatic reset only (non-latching), when input passes the reset
point.
2. Automatic + manual reset at any time (non-latching).
3. Manual reset only, at any time (latching).
4. Manual reset only after alarm condition has cleared (latching).
Note: Front panel button or digital input may be assigned to acknowledge
relays programmed for manual reset.
Time Delay: 0 to 999.9 seconds, on & off relay time delays.
Programmable and independent for each relay.
Fail-Safe Operation: Programmable and independent for each relay.
Note: Relay coil is energized in non-alarm condition. In case of
power failure, relay will go to alarm state.
Auto Initialization:When power is applied to the meter, relays
will reflect the state of the input to the meter.
Serial Communications
Protocol: Modbus® RTU
Meter Address/Slave ID: 1 - 247
Baud Rate: 300 - 19,200 bps
Transmit Time Delay: Programmable between 0 and 199 ms or transmitter
always on for RS-422 communication
Data: 8 bit (1 start bit, 1 or 2 stop bits)
Parity: Even, odd, or none with 1 or 2 stop bits
Byte-to-Byte Timeout: 0.01 - 2.54 seconds
Turn Around Delay: Less than 2 ms (fixed)
Note: Refer to the PD6000/PD7000 Modbus Register Tables for details
Isolated 4-20 mA Transmitter Output
Output Source: Process variable (PV), max, min, set points 1-8,
manual control setting, or Modbus input
Scaling Range: 1.000 to 23.000 mA for any display range
Calibration: Factory calibrated: 4.000 to 20.000 = 4-20 mA output
Analog Output Programming: 23.000 mA maximum for all parameters:
Overrange, underrange, max, min, and break
Accuracy: ± 0.1% of span ± 0.004 mA
Temperature Drift: 0.4 µA/°C max from 0 to 65°C
ambient, 0.8 µA/°C max from -40 to 0°C ambient
Note: Analog output drift is separate from input drift.
Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC
± 10%. Isolated from the input at >500 V. May be used
to power the 4-20 mA output or other devices. All models rated @
40 mA max.
Digital I/O Expansion
Module
Channels: 4 digital inputs & 4 digital outputs per module
System: Up to 2 modules for a total of 8 inputs & 8 outputs
Digital Input Logic: High: 3 to 5 VDC Low: 0 to 1.25 VDC
Digital Output Logic: High: 3.1 to 3.3 VDC Low: 0 to 0.4 VDC
Source Current: 10 mA maximum
Sink Current: 1.5 mA minimum
+5 V Terminal: To be used as pull-up for digital inputs only
4-Relay Expansion Module
Relays: (4) Form A (SPST) rated 3 A @ 30 VDC and 125/250 VAC resistive
load; 1/14 HP (approx. 50 watts) @ 125/250 VAC for inductive loads
Metex Corporation Limited has been providing superior products and services to the process control, chemical treatment, waste water, industrial and manufacturing industries for over 25 years. It is our goal to continually provide our customers with the best possible equipment, technology, and service.
Dataloggers, sensors, pumps, recorders, hand held instruments, flow instrumentation, level controls, valves, instrumentation, containers, tanks, transmitters, data loggers, digital indicators, mixers and agitators, pressure intrumentation, analyzers and controllers for a variety of industrial applications such as water quality, pH/ORP and more.
Website Content
Water Analyzers and Controllers, Wireless Products, Corrosion Monitoring Equipment, Cooling Tower and Boiler Controllers, a wide variety of Pumps, Valves, Dataloggers and Recorders, HVAC, Instrumentation, Skids and Systems, Containers and Tanks from world leading manufacturers are products you will find on this site.