PD6000 Process Meter - ProVu Series 1/8 DIN Digital Panel Meters

USA Toll Free: 1-800-730-0302 Tel: 416-240-1920 - sales@metexcorporation.com


The PD6000 is a member of the ProVu series of 1/8 DIN digital panel meters that accepts a process current (4-20 mA) or process voltage (0-5V, 1-5V, etc.) signal. It displays that signal on a dual-line, 6-digit display that is available with optional Sunbright® sunlight readable LEDs. Like all ProVu meters, the PD6000 includes UL / C-UL listing and CE marking, a NEMA 4X front, and AC or DC power options. ProVu meters can be equipped with up to four internal relays, a 4-20 mA output and Modbus® RTU serial communications. The PD6000 includes a 24 VDC power supply to drive the transmitter and can be programmed via the front panel pushbuttons or with the onboard USB and MeterView® Pro software.

Features

  • 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs
  • NEMA 4X, IP65 Front
  • Universal 85-265 VAC or 12-24 VDC Input Power
  • Large Dual-Line 6-Digit Display, 0.60" & 0.46"
  • Dual-Scale for Level Applications – Single Input
  • Optional SunBright Display Models for Outdoor Applications
  • Isolated 24 VDC @ 200 mA Transmitter Power Supply
  • Signal Input Conditioning for Flow & Round Horizontal Tanks
  • Programmable Displays & Function Keys
  • 32-Point, Square Root, or Exponential Linearization
  • Multi-Pump Alternation Control
  • 2 or 4 Relays + Isolated 4-20 mA Output Options
  • External 4-Relay & Digital I/O Expansion Modules
  • USB, RS-232, & RS-485 Serial Communication Options
  • Tare Function
  • Modbus RTU Communication Protocol Standard
  • On-Board Digital Input
  • Configure, Monitor, and Datalog
  • Onboard USB and MeterView® Pro Programming Software

PD6000 ProVu Process Meter Data Sheet
PD6000 ProVu Process Meter Instruction Manual

General Specifications

  • Display: Upper display: 0.60" (15 mm) high. Lower display: 0.46" (12 mm) high. Both are 6 digits (-99999 to 999999), red LEDs.
  • Display Intensity: Eight intensity levels
  • Display Update Rate: 5/second (200 ms)
  • Overrange: Display flashes 999999
  • Underrange: Display flashes -99999
  • Display Assignment: The upper and lower displays may be assigned to PV1, PV2, PCT (percent), d r-u, d gross, d nt-g, max/min, alternate max & min, set points, units (lower display only), or Modbus input.
  • Front Panel: NEMA 4X, IP65
  • Programming Methods: Four front panel buttons, digital inputs, PC and MeterView Pro software, Modbus registers.
  • F4 Digital Input Contacts: 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
  • F4 Digital Input Logic Levels: Logic High: 3 to 5 VDC
  • Logic Low: 0 to 1.25 VDC
  • Noise filter: Programmable from 2 to 199 (0 will disable filter)
  • Filter Bypass: Programmable from 0.1 to 99.9% of calibrated span
  • Recalibration: Calibrated at the factory. Recalibration is recommended at least every 12 months.
  • Max/Min Display: Max / min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
  • Password: Three programmable passwords restrict modification of programmed settings.
  • Non-Volatile Memory: All programmed settings are stored in nonvolatile memory for a minimum of ten years if power is lost.
  • Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max or 12-24 VDC ± 10%, 15 W max. Powered over USB for configuration only.
  • Fuse: Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse.
  • Isolated Transmitter Power Supply:Terminals P+ & P-: 24 VDC ± 10%. 12-24 VDC powered models selectable for 24, 10, or 5 VDC supply (internal P+/P- switch). 85-265 VAC models rated @ 200 mA max, 12-24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply.
  • Normal Mode Rejection: Greater than 60 dB at 50/60 Hz
  • Isolation: 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply.
  • Overvoltage Category: Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
  • Environmental:
    Operating temperature range: -40 to 65°C
    Storage temperature range: -40 to 85°C
    Relative humidity: 0 to 90% non-condensing
  • Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
  • Enclosure: 1/8 DIN, high impact plastic, UL 94V-0, color: black
  • Mounting: 1/8 DIN panel cutout required: 3.622" x 1.772" (92 mm x 45 mm). Two panel mounting bracket assemblies are provided.
  • Tightening Torque: Screw terminal connectors: 5 lb-in (0.56 Nm)
  • Dimensions: 4.68" x 2.45" x 5.64" (119 mm x 62 mm x 143 mm) (W x H x D)
  • Weight: 9.5 oz (269 g)
  • UL File Number: UL & C-UL Listed. E160849; 508 Industrial Control Equipment.
  • Warranty: 3 years parts&labor
  • USB Connection: Compatibility: USB 2.0 Standard, Compliant
  • Connector Type: Micro-B receptacle
  • Cable: USB A Male to Micro-B Cable
  • Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit,
  • Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit
  • Power: USB Port

Process Input

  • Inputs: Field selectable: 0-20, 4-20 mA, ±10 VDC (0-5, 1-5, 0-10 V), Modbus PV (Slave)
  • Accuracy: ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span
  • Temperature Drift: 0.005% of calibrated span/°C max from 0 to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 0°C ambient
  • Signal Input Conditioning: Linear, square root, programmable exponent, or round horizontal tank volume calculation.
  • Multi-Point Linearization: 2 to 32 points for PV or PV1. 2 to 8 points for PV2 (Dual-Scale Level feature)
  • Programmable Exponent: 1.0001 to 2.9999
  • Low-Flow Cutoff: 0-999999 (0 disables cutoff function)
  • Decimal Point: Up to five decimal places or none: d.ddddd, dd.dddd,ddd.ddd, dddd.dd, ddddd.d, or dddddd.
  • Calibration Range: 4-20 mA: minimum span input 1 & input 2: 0.15 mA. ±10 V: minimum span input 1 & 2: 0.10 V. An Error message will appear if input 1 and input 2 signals are too close together.
  • Input Impedance: Voltage ranges: greater than 500 kO. Current ranges: 50 - 100 O (depending on resettable fuse impedance).
  • Input Overload:Current input protected by resettable fuse, 30 VDC max.
  • HART Transparency: Analog input will not interfere with existing HART communications on the wired 4-20 mA signal

Relays

  • Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (˜ 50 watts) @ 125/250 VAC for inductive loads such as contactors, solenoids, etc.
  • Noise Suppression: Noise suppression is recommended for each relay contact switching inductive loads.
  • Deadband: 0-100% of span, user programmable
  • High or Low Alarm: User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turned off).
  • Relay Operation: automatic (non-latching), latching (requires manual acknowledge), sampling (based on time), pump alternation control (2 to 8 relays), Off (disable unused relays and enable interlock feature, manual on/off control mode).
  • Relay Reset: User selectable via front panel buttons or digital inputs.
    1. Automatic reset only (non-latching), when input passes the reset point.
    2. Automatic + manual reset at any time (non-latching).
    3. Manual reset only, at any time (latching).
    4. Manual reset only after alarm condition has cleared (latching).
    Note: Front panel button or digital input may be assigned to acknowledge relays programmed for manual reset.
  • Time Delay: 0 to 999.9 seconds, on & off relay time delays. Programmable and independent for each relay.
  • Fail-Safe Operation: Programmable and independent for each relay.
    Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
  • Auto Initialization:When power is applied to the meter, relays will reflect the state of the input to the meter.

Serial Communications

  • Protocol: Modbus® RTU
  • Meter Address/Slave ID: 1 - 247
  • Baud Rate: 300 - 19,200 bps
  • Transmit Time Delay: Programmable between 0 and 199 ms or transmitter always on for RS-422 communication
  • Data: 8 bit (1 start bit, 1 or 2 stop bits)
  • Parity: Even, odd, or none with 1 or 2 stop bits
  • Byte-to-Byte Timeout: 0.01 - 2.54 seconds
  • Turn Around Delay: Less than 2 ms (fixed)
    Note: Refer to the PD6000/PD7000 Modbus Register Tables for details
  • Isolated 4-20 mA Transmitter Output
  • Output Source: Process variable (PV), max, min, set points 1-8, manual control setting, or Modbus input
  • Scaling Range: 1.000 to 23.000 mA for any display range
  • Calibration: Factory calibrated: 4.000 to 20.000 = 4-20 mA output
  • Analog Output Programming: 23.000 mA maximum for all parameters:
  • Overrange, underrange, max, min, and break
  • Accuracy: ± 0.1% of span ± 0.004 mA
  • Temperature Drift: 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient
    Note: Analog output drift is separate from input drift.
  • Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC ± 10%. Isolated from the input at >500 V. May be used to power the 4-20 mA output or other devices. All models rated @ 40 mA max.

Digital I/O Expansion Module

  • Channels: 4 digital inputs & 4 digital outputs per module
  • System: Up to 2 modules for a total of 8 inputs & 8 outputs
  • Digital Input Logic: High: 3 to 5 VDC Low: 0 to 1.25 VDC
  • Digital Output Logic: High: 3.1 to 3.3 VDC Low: 0 to 0.4 VDC
  • Source Current: 10 mA maximum
  • Sink Current: 1.5 mA minimum
  • +5 V Terminal: To be used as pull-up for digital inputs only

4-Relay Expansion Module

  • Relays: (4) Form A (SPST) rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (approx. 50 watts) @ 125/250 VAC for inductive loads

| Senix Process Meter Accessories

 

METEX CORPORATION LIMITED

About Us

Metex Corporation Limited has been providing superior products and services to the process control, chemical treatment, waste water, industrial and manufacturing industries for over 25 years. It is our goal to continually provide our customers with the best possible equipment, technology, and service.

Sitemap

Our Products

Dataloggers, sensors, pumps, recorders, hand held instruments, flow instrumentation, level controls, valves, instrumentation, containers, tanks, transmitters, data loggers, digital indicators, mixers and agitators, pressure intrumentation, analyzers and controllers for a variety of industrial applications such as water quality, pH/ORP and more.

Website Content

Water Analyzers and Controllers, Wireless Products, Corrosion Monitoring Equipment, Cooling Tower and Boiler Controllers, a wide variety of Pumps, Valves, Dataloggers and Recorders, HVAC, Instrumentation, Skids and Systems, Containers and Tanks from world leading manufacturers are products you will find on this site.

Get in Touch