PD6060 ProVu Dual Analog Input Process Digital Panel Meter

USA Toll Free: 1-800-730-0302 Tel: 416-240-1920 - sales@metexcorporation.com


The PD6060 is a member of the ProVu series of 1/8 DIN digital panel meters that accepts two inputs of either a process current (4-20 mA) or process voltage (0-5V, 1-5V, etc.) signal. It displays these signals on a dual line, 6-digit display that is available with an optional Sunbright® sunlight readable LEDs. The meter can be customized such that these two inputs are displayed in a variety of ways, including both at the same time with tags or the result of math functions performed on one or both of the inputs. Like all ProVu meters, the PD6060 includes UL / C-UL listing and CE marking, a NEMA 4X front, and AC or DC power options. The PD6060 can also be equipped with up to four internal relays, a 4-20 mA analog output, and Modbus® serial communications. The PD6060 includes a 24 V DC power supply to drive the transmitters. ProVu meters can be programmed via the front panel pushbuttons or free MeterView® Pro software.

Features

  • Dual-Input Process Meter with Math Functions
  • Addition, Difference, Average, Multiplication, Division, Min, Max, Weighted Average, Ratio, Concentration, & More
  • 0-20 mA, 4-20 mA, 0-5 V, 1-5 V, and ±10 V Inputs
  • Large Dual-Line 6-Digit Display, 0.60" & 0.46"
  • Optional SunBright Display Models for Outdoor Applications
  • NEMA 4X, IP65 Front
  • Universal 85-265 VAC, or 12-24 VDC Input Power Models
  • Isolated 24 VDC @ 200 mA Transmitter Power Supply
  • Programmable Display & Function Keys
  • 32-Point, Square Root, or Exponential Linearization
  • Multi-Pump Alternation Control
  • 2 or 4 Relays + Isolated 4-20 mA Output Options
  • External 4-Relay & Digital I/O Expansion Modules
  • USB, RS-232, & RS-485 Serial Communication Options
  • Modbus RTU Communication Protocol Standard
  • On-Board Digital Input
  • Onboard USB and MeterView® Pro Programming Software

PD6060 ProVu Dual Analog Input Process Digital Panel Meter Data Sheet
PD6060 ProVu Dual Analog Input Process Digital Panel Meter Instruction Manual

General Specifications

  • Display: Upper display: 0.60" (15 mm) high. Lower display: 0.46" (12 mm) high. Both are 6 digits (-99999 to 999999), red LEDs
  • Display Intensity: Eight user selectable intensity levels
  • Display Update Rate: 5/second (200 ms)
  • Overrange: Display flashes 999999
  • Underrange: Display flashes -99999
  • Display Assignment: The Upper and Lower displays may be assigned to process values for Channels A (Ch-A), B (Ch-B), or C (Ch-C), toggle between (Ch-A & Ch-B, Ch-A & Ch-C, Ch-B & Ch-C, and Ch-A, Ch-B, & Ch-C), toggle between Channel & units, show channel gross value (no tare) or toggle net (tare) and gross values, show relay set points, max & min values, or
  • Modbus input. The second display may also be set to show engineering units or be off, with no display.
  • Front Panel: NEMA 4X, IP65
  • Programming Methods: Four front panel buttons, digital inputs, PC and MeterView Pro software, Modbus registers
  • F4 Digital Input Contacts: 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
  • F4 Digital Input Logic Levels: Logic High: 3 to 5 VDC
  • Noise filter: Programmable from 2 to 199 (0 will disable filter)
  • Filter Bypass: Programmable from 0.1 to 99.9% of calibrated span
  • Recalibration: All ranges are calibrated at the factory. Recalibration is recommended at least every 12 months.
  • Max/Min Display: Max (Peak) / min (Valley) readings reached by the process are stored until reset by the user or until power to the meter is cycled.
  • Password: Three programmable passwords restrict modification of programmed settings.
  • Non-Volatile Memory: All programmed settings are stored in non-volatile memory for a minimum of ten years if power is lost.
  • Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max, or optional model with 12-24 VDC ±10%, 15 W max.
  • Fuse: Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse.
  • Isolated Transmitter Power Supply: Terminals P+ & P-: 24 VDC ± 10%. Internally selectable jumper for 24, 10, or 5 VDC supply.
  • 85-265 VAC models rated @ 200 mA max, 12-24 VDC powered models rated @ 100 mA max, @ 50 mA max for 5 or 10 VDC supply.
  • Normal Mode Rejection: Greater than 60 dB at 50/60 Hz
  • Isolation: 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply.
  • Overvoltage Category: Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
  • Environmental: Operating temperature range: -40 to 65°C
  • Storage temperature range: -40 to 85°C
  • Relative humidity: 0 to 90% non-condensing
  • Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
  • Enclosure: 1/8 DIN, high impact plastic, UL 94V-0, color: black
  • Mounting: 1/8 DIN panel cutout required: 3.622" x 1.772"
    (92 mm x 45 mm). Two panel mounting bracket assemblies are provided.
  • Tightening Torque: Screw terminal connectors: 5 lb-in (0.56 Nm)
  • Overall Dimensions: 4.68" x 2.45" x 5.64"
    (119 mm x 62 mm x 143 mm) (W x H x D)
  • Weight: 9.5 oz (269 g)
  • UL File Number: UL & c-UL Listed. E160849; 508 Industrial Control Equipment.
  • Warranty: 3 years parts & labor
  • USB Connection: Compatibility: USB 2.0 Standard, Compliant
  • Connector Type: Micro-B receptacle
  • Cable: USB A Male to Micro-B Cable
  • Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit, Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit
  • Power: USB Port

Dual Process Input

  • Inputs: Two non-isolated inputs, each separately field selectable:
  • 0-20, 4-20 mA, 10 V (0-5, 1-5, 0-10 V), Modbus PV (Slave)
  • Channels: Channel A, Channel B, Channel C (Math channel)
    Programmable Constants: Constant P (Adder): -99999 to 999999, default: 0.000; Constant F (Factor): 0.00001 to 999999, default: 1.000
  • Math Functions: Addition, difference, absolute difference, average, multiplication, division, max of A or B, min of A or B, draw, weighted average, ratio, concentration. See instruction manual for details.
  • Sequence of Operations for Input Programing:
    1.Select Input for A and B
    2.Set up the engineering units for A, B, and C
    3.Set up decimal point for A, B, and C
    4.Scale A & B
    5.Set up the displays for A, B, or C
    6.Select the transfer function for A & B (e.g. Linear)
    7.Select Math function for Channel C
    8.Program constants for Factor (F) and Adder (P).
    9.Program cutoff values for A and B
  • Accuracy: ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span
  • Temperature Drift: 0.005% of calibrated span/°C max from 0 to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 0°C ambient
  • Signal Input Conditioning: Linear, square root, programmable exponent, or round horizontal tank volume calculation.
  • Multi-Point Linearization: 2 to 32 points for channel A and B
  • Programmable Exponent: 1.0001 to 2.9999
  • Low-Flow Cutoff: 0-999999 (0 disables cutoff function)
  • Decimal Point: Up to five decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd.
  • Calibration Range: 4-20 mA: minimum span input 1 & input 2: 0.15 mA. ±10 V: minimum span input 1 & 2: 0.10 V. An Error message will appear if input 1 and input 2 signals are too close together.
  • Input Impedance: Voltage ranges: greater than 500 kO. Current ranges: 50 - 100 O (depending on resettable fuse impedance).
  • Input Overload: Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed.
  • HART Transparency: Analog input will not interfere with existing HART communications on the wired 4-20 mA signal

Relays

  • Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (˜ 50 W) @ 125/250 VAC for inductive loads.
  • Noise Suppression: Noise suppression is recommended for each relay contact switching inductive loads.
  • Deadband: 0-100% of span, user programmable
  • High or Low Alarm: User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turned off).
  • Relay Operation: automatic (non-latching), latching (requires manual acknowledge), sampling (based on time), pump alternation control (2 to 8 relays), Off (disable unused relays and enable interlock feature, manual on/off control mode).
  • Relay Reset: User selectable via front panel buttons or digital inputs.
    1.Automatic reset only (non-latching), when input passes the reset point.
    2.Automatic + manual reset at any time (non-latching).
    3.Manual reset only, at any time (latching).
    4.Manual reset only after alarm condition has cleared (latching).
    Note: Front panel button or digital input may be assigned to acknowledge relays programmed for manual reset.
  • Time Delay: 0 to 999.9 seconds, on & off relay time delays. Programmable and independent for each relay.
  • Fail-Safe Operation: Programmable and independent for each relay. Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
  • Auto Initialization: When power is applied to the meter, relays will reflect the state of the input to the meter.

Serial Communications

  • Protocol: Modbus® RTU
  • Meter Address/Slave ID: 1 - 247
  • Baud Rate: 300 - 19,200 bps
  • Transmit Time Delay: Programmable between 0 and 199 ms
  • Data: 8 bit (1 start bit, 1 or 2 stop bits)
  • Parity: Even, odd, or none with 1 or 2 stop bits
  • Byte-to-Byte Timeout: 0.01 - 2.54 seconds
  • Turn Around Delay: Less than 2 ms (fixed)
    Note: Refer to the ProVu Modbus Register Tables located at www.predig.com for details.

Isolated 4-20 mA Transmitter Output

  • Output Source: Process channel A, B, or C, max or min for channel A, B, or highest or lowest max or min of A and B, set points 1-8, Modbus input, or manual control mode
  • Scaling Range: 1.000 to 23.000 mA for any display range
  • Calibration: Factory calibrated: 4.000 to 20.000 = 4-20 mA output
  • Analog Output Programming: 23.000 mA maximum for all parameters: Overrange, underrange, max, min, and break
  • Accuracy: ±0.1% of span ±0.004 mA
  • Temperature Drift: 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µ/°C max from -40 to 0°C ambient
    Note: Analog output drift is separate from input drift.
  • Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC ± 10%. Isolated from the input at >500 V. May be used to power the 4-20 mA output or other devices. All models rated @ 40 mA max.
  • External Loop Power Supply: 35 VDC maximum

Digital I/O Expansion Module

  • Channels: 4 digital inputs & 4 digital outputs per module
  • System: Up to 2 modules for a total of 8 inputs & 8 outputs
  • Digital Input Logic: High: 3 to 5 VDC Low: 0 to 1.25 VDC
  • Digital Output Logic: High: 3.1 to 3.3 VDC Low: 0 to 0.4 VDC
  • Source Current: 10 mA maximum
  • Sink Current: 1.5 mA minimum
  • +5 V Terminal: To be used as pull-up for digital inputs only.

4-Relay Expansion Module

  • Relays: Four Form A (SPST) rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (˜50 watts) @ 125/250 VAC for inductive load

 

METEX CORPORATION LIMITED

About Us

Metex Corporation Limited has been providing superior products and services to the process control, chemical treatment, waste water, industrial and manufacturing industries for over 25 years. It is our goal to continually provide our customers with the best possible equipment, technology, and service.

Sitemap

Our Products

Dataloggers, sensors, pumps, recorders, hand held instruments, flow instrumentation, level controls, valves, instrumentation, containers, tanks, transmitters, data loggers, digital indicators, mixers and agitators, pressure intrumentation, analyzers and controllers for a variety of industrial applications such as water quality, pH/ORP and more.

Website Content

Water Analyzers and Controllers, Wireless Products, Corrosion Monitoring Equipment, Cooling Tower and Boiler Controllers, a wide variety of Pumps, Valves, Dataloggers and Recorders, HVAC, Instrumentation, Skids and Systems, Containers and Tanks from world leading manufacturers are products you will find on this site.

Get in Touch