PD8-6000 ProtEX-MAX Explosion-Proof Process Meter

USA Toll Free: 1-800-730-0302 Tel: 416-240-1920 - sales@metexcorporation.com



The ProtEX-MAX™ PD8-6000 explosion-proof process meter offers all the functionality of the ProVu PD6000 as a fully FM, CSA, ATEX, and IECEx approved explosion-proof product. It accepts a process current (4-20 mA) or process voltage (0-5V, 1-5V, etc.) signal and displays it on a dual-line, 6-digit Sunbright® sunlight readable display. The meter includes a 24 VDC power supply to drive the transmitter and can be equipped with up to four internal relays and a 4-20 mA output. The PD8-6000 can be programmed and operated without opening the housing by using the built-in SafeTouch® through-glass buttons or the RS485 serial communication port with free Modbus® protocol.

Quick Overview

  • Input: 0-20 mA, 4-20 mA; ±10 VDC
  • (0-5, 1-5, 0-10 V); Modbus PV (slave)
  • Display: Dual-line 6-digit, 0.60" (15 mm) & 0.46" (12 mm)
  • Enclosure: Smooth die-cast aluminum explosion-proof; NEMA 4X, 7, 9/IP68
  • Power: 85-265 VAC or 12-24 VDC option
  • Operating Temperature: -40 to 65°C

Features

  • SunBright Display Standard
  • Dual-Scale for some Level Applications – Single Input
  • Signal Input Conditioning for Flow & Round Horizontal Tanks
  • 32-Point, Square Root, or Exponential Linearization
  • Multi-Pump Alternation Control
  • Tare Function
  • SafeTouch® through-glass button programming
  • Modbus RS-485 serial communications
  • Flanges for wall or pipe mounting
  • Isolated 24 VDC @ 25 mA transmitter power supply
  • Onboard USB and MeterView® Pro Programming Software

PD8-6000 ProtEX-MAX Explosion-Proof Process Meter Data Sheet

PD8-6000 ProtEX-MAX Explosion-Proof Process Meter Instruction Manual

General Specifications

  • Display: Upper display: 0.60" (15 mm) high. Lower display: 0.46" (12 mm) high. Both are 6 digits (-99999 to 999999), red LEDs.
  • Display Intensity: Eight intensity levels
  • Display Update Rate: 5/second (200 ms)
  • Overrange: Display flashes 999999
  • Underrange: Display flashes -99999
  • Display Assignment: The upper and lower displays may be assigned to PV1, PV2, PCT (percent), max/min, alternate max & min, set points, units (lower display only), or Modbus input.
  • Programming Methods: Four through-glass SafeTouch buttons, four mechanical buttons behind glass, digital inputs, PC and MeterView Pro software, or Modbus registers.
  • F4 Digital Input Contacts: 3.3 VDC on contact. Connect normally open contacts across F4 to COM.
  • F4 Digital Input Logic Levels: Logic High: 3 to 5 VDC; Logic Low: 0 to 1.25 VDC
  • Noise filter: Programmable from 2 to 199 (0 will disable filter)
  • Filter Bypass: Programmable from 0.1 to 99.9% of calibrated span
  • Recalibration: Calibrated at the factory. Recalibration is recommended at least every 12 months.
  • Max/Min Display: Max / min readings reached by the process are stored until reset by the user or until power to the meter is turned off.
  • Password: Three programmable passwords restrict modification of programmed settings.
  • Non-Volatile Memory: All programmed settings are stored in nonvolatile memory for a minimum of ten years if power is lost.
  • Power Options: 85-265 VAC 50/60 Hz, 90-265 VDC, 20 W max, or optional model with 12-24 VDC ±10%, 15 W max.
  • Fuse: Required external fuse: UL Recognized, 5 A max, slow blow; up to 6 meters may share one 5 A fuse.
  • Isolated Transmitter Power Supply: Terminals P+ & P-: 24 VDC ± 10%. Isolated from the input at >500 V. Jumper selectable for 24, 10, or 5 VDC supply (internal jumper J4). All models transmitter supply rated @ 25mA max.
  • Normal Mode Rejection: Greater than 60 dB at 50/60 Hz
  • Isolation: 4 kV input/output-to-power line. 500 V input-to-output or output-to-P+ supply.
  • Overvoltage Category: Installation Overvoltage Category II: Local level with smaller transient overvoltages than Installation Overvoltage Category III.
  • Environmental:
    T6 Class operating temperature range Ta = -40 to 60°C
    T5 Class operating temperature range Ta = -40 to 65°C
  • Max Power Dissipation: Maximum power dissipation limited to 15.1 W.
  • Connections: Removable screw terminal blocks accept 12 to 22 AWG wire, RJ45 for external relays, digital I/O, and serial communication adapters.
  • Enclosure: Explosion-proof die cast aluminum with glass window, corrosion resistant epoxy coating, color: blue. NEMA 4X, 7, & 9, IP68. Default conduit connections: Four ¾" NPT threaded conduit openings and two ¾" NPT metal conduit plugs with 12 mm hex key fitting installed. Additional conduit opening configurations may be available; verify quantity and sizes on specific device labeling during installation.
  • Mounting: Four slotted flanges for wall mounting or NPS 1½" to 2½" or DN 40 to 65 mm pipe mounting.
  • Dimensions: 6.42" x 7.97" x 8.47" (W x H x D) (163 mm x 202 mm x 215 mm)
  • Weight: 16.0 lbs (7.26 kg)
  • Warranty: 3 years parts & labor
  • USB Connection: Compatibility: USB 2.0 Standard, Compliant
    Connector Type: Micro-B receptacle
    Cable: USB A Male to Micro-B Cable
    Driver: Windows 98/SE, ME, 2000, Server 2003/2008, XP 32/64-Bit,
    Vista 32/64-Bit, Windows 7 32/64-Bit, Windows 10 32/64-Bit
    Power: USB Port

Process Inputs

  • Inputs: Field selectable: 0-20, 4-20 mA, ±10 VDC (0-5, 1-5, 0-10 V), Modbus PV (Slave)
  • Accuracy: ±0.03% of calibrated span ±1 count, square root & programmable exponent accuracy range: 10-100% of calibrated span
  • Temperature Drift: 0.005% of calibrated span/°C max from 0 to 65°C ambient, 0.01% of calibrated span/°C max from -40 to 0°C ambient
  • Signal Input Conditioning: Linear or round horizontal tank volume calculation.
  • Multi-Point Linearization: 2 to 32 points for PV or PV1. 2 to 8 points for PV2 (Dual-Scale Level feature)
  • Programmable Exponent: 1.0001 to 2.9999
  • Low-Flow Cutoff: 0-999999 (0 disables cutoff function)
  • Decimal Point: Up to five decimal places or none: d.ddddd, dd.dddd, ddd.ddd, dddd.dd, ddddd.d, or dddddd.
  • Calibration Range: 4-20 mA: minimum span input 1 & input 2: 0.15 mA. ±10 V: minimum span input 1 & 2: 0.10 V. An Error message will appear if input 1 and input 2 signals are too close together.
  • Input Impedance: Voltage ranges: greater than 1 M?. Current ranges: 50 - 100 ? (depending on resettable fuse impedance).
  • Input Overload: Current input protected by resettable fuse, 30 VDC max. Fuse resets automatically after fault is removed.
  • HART Transparency: Analog input will not interfere with existing HART communications on the wired 4-20 mA signal

Relays

  • Rating: 2 or 4 SPDT (Form C) internal and/or 4 SPST (Form A) external; rated 3 A @ 30 VDC and 125/250 VAC resistive load; 1/14 HP (˜ 50 watts) @ 125/250 VAC for inductive loads such as contactors, solenoids, etc.
  • Noise Suppression: Noise suppression is recommended for each relay contact switching inductive loads.
  • Deadband: 0-100% of span, user programmable
  • High or Low Alarm: User may program any alarm for high or low trip point. Unused alarm LEDs and relays may be disabled (turned off).
  • Relay Operation: Automatic (non-latching), latching (requires manual acknowledge), sampling (based on time), pump alternation control (2 to 8 relays), Off (disable unused relays and enable interlock feature, manual on/off control mode).
  • Relay Reset: User selectable via front panel buttons or digital inputs.
    1. Automatic reset only (non-latching), when input passes the reset point.
    2. Automatic + manual reset at any time (non-latching).
    3. Manual reset only, at any time (latching).
    4. Manual reset only after alarm condition has cleared (latching).
    Note: Front panel button or digital input may be assigned to acknowledge relays programmed for manual reset.
  • Time Delay: 0 to 999.9 seconds, on & off relay time delays. Programmable and independent for each relay.Fail-Safe Operation: Programmable and independent for each relay.
    Note: Relay coil is energized in non-alarm condition. In case of power failure, relay will go to alarm state.
  • Auto Initialization: When power is applied to the meter, relays will reflect the state of the input to the meter.

Isolated 4-20 mA Transmitter Output

  • Output Source: Process variable (PV), max, min, set points 1-8, manual control setting, or Modbus input
  • Scaling Range: 1.000 to 23.000 mA for any display range
  • Calibration: Factory calibrated: 4.000 to 20.000 = 4-20 mA output
  • Analog Output Programming: 23.000 mA maximum for all parameters:Overrange, underrange, max, min, and break
  • Accuracy: ± 0.1% of span ± 0.004 mA
  • Temperature Drift: 0.4 µA/°C max from 0 to 65°C ambient, 0.8 µA/°C max from -40 to 0°C ambient
    Note: Analog output drift is separate from input drift.
  • Isolated Transmitter Power Supply: Terminals I+ & R: 24 VDC ± 10%. Isolated from the input at >500 V. May be used to power the 4-20 mA output or other devices. All models @ 25 mA max.

Digital Inputs and Outputs

  • Channels: 4 digital inputs & 4 digital outputs per module
  • System: One expansion module may be added for a total of 8 inputs & 8 outputs
    Note: The jumper located between the RJ45 connectors must be removed on the expansion module.
  • Digital Input Logic: High: 3 to 5 VDC;Low: 0 to 1.25 VDC
  • Digital Output Logic: High: 3.1 to 3.3 VDC; Low: 0 to 0.4 VD
  • Source Current: 10 mA maximum output current
  • Sink Current: 1.5 mA minimum input current
  • +5 V Terminal: To be used as pull-up for digital inputs only. Connect normally open pushbuttons across +5 V & DI 1-4. Warning: DO NOT use +5 V terminal (pin 1) to power external devices.
  • Function Assignment: The on-board digital inputs (1-4) are designed to mimic the behavior of the front panel buttons (Menu, F1, F2, & F3). If you wish to change their behavior, re-assign
  • F1-F3 to the desired function, then change the corresponding digital input to match.

Product Ratings and Approvals

  • FM Enclosure:Type 4X; IP66
    Class I, Division 1, Groups B, C, D
    Class II, Division 1, Groups E, F, G
    Class III, Division 1, T5/T6
    Class I, Zone 1, AEx d, IIC Gb T5/T6
    Zone 21, AEx tb IIIC T90°C; Ta -40°C to +65°C
    T6 Ta = -40°C to +60°C; T5 Ta = -40°C to +65°C
    Certificate Number: 3047283
  • CSA: Class I, Division 1, Groups B, C, D
    Class II, Division 1, Groups E, F, G
    Class III, Division 1
    Class I Zone 1 Ex d IIC
    Zone 21 Ex tb IIIC T90°C
    -40°C < Tamb. < +60° C; Temperature Code T6
    -40°C < Tamb. < +65° C; Temperature Code T5
    Enclosure Type 4X & IP66
    Certificate Number: 2531731
  • ATEX: II 2 G D Ex d IIC T* Gb
    Ex tb IIIC T90°C Db IP68
    Ta = -40°C to +*°C
    *T6 = -40°C to +60°C
    *T5 = -40°C to +65°C
    Certificate number: Sira 12ATEX1182
  • IECEx: Ex d IIC T* Gb
    Ex tb IIIC T90°C Db IP68
    Ta = -40°C to +*°C
    *T6 = -40°C to +60°C
    *T5 = -40°C to +65°C
    Certificate Number: IECEx SIR 12.0073

METEX CORPORATION LIMITED

About Us

Metex Corporation Limited has been providing superior products and services to the process control, chemical treatment, waste water, industrial and manufacturing industries for over 25 years. It is our goal to continually provide our customers with the best possible equipment, technology, and service.

Sitemap

Our Products

Dataloggers, sensors, pumps, recorders, hand held instruments, flow instrumentation, level controls, valves, instrumentation, containers, tanks, transmitters, data loggers, digital indicators, mixers and agitators, pressure intrumentation, analyzers and controllers for a variety of industrial applications such as water quality, pH/ORP and more.

Website Content

Water Analyzers and Controllers, Wireless Products, Corrosion Monitoring Equipment, Cooling Tower and Boiler Controllers, a wide variety of Pumps, Valves, Dataloggers and Recorders, HVAC, Instrumentation, Skids and Systems, Containers and Tanks from world leading manufacturers are products you will find on this site.

Get in Touch